CHINT · Motor overload relay
Product overview
CHINT 837108 NXR-25 is a three-pole overload relay with an adjustable current range of 0.4–0.63 A. It provides overload and phase-loss protection for AC motor starters, with temperature compensation, trip indication, stop/test functions and manual or automatic reset.
Technical selection summary
| Ordering code | 837108 |
|---|---|
| Manufacturer model | NXR-25 0.4-0.63A |
| Current setting range | 0.4–0.63 A |
| Frame current | 25 A |
| Main circuit poles | 3P |
| Trip class | 10A |
| Auxiliary contacts | 1NO+1NC; electrically separate |
| Contact terminals | 97–98 NO; 95–96 NC |
| Rated insulation voltage Ui | 690 V |
| Circuit frequency | 50/60 Hz |
| Protection functions | Motor overload and phase loss |
| Reset mode | Manual / automatic |
| Operating functions | Stop, test and trip indication |
| Temperature compensation | Yes |
| Construction | Three-phase bimetallic thermal relay |
| Mounting | Direct plug-in to compatible NXC contactors; independent mounting with MB-2 base |
| Compatible contactors | NXC-06, 09, 12, 16, 18, 22, 25, 32 and 38 |
| Recommended short-circuit backup fuse | 2 A gG (RT16 recommended) |
| Auxiliary contact rating AC-15 | 1.5 A at 380/400/415 V AC |
| Auxiliary contact rating DC-13 | 0.2 A at 220 V DC |
| Normal ambient temperature | −5 °C to +40 °C; 24-hour average ≤+35 °C |
| Altitude | ≤2000 m |
| Installation category / pollution degree | III / 3 |
| Reference standards | IEC/EN 60947-4-1; IEC/EN 60947-5-1 |
| Front protection degree | IP20 |
Typical applications
- AC motor starters
- Machine protection circuits
- Contactor-and-relay sets