CHINT · Surge protective device
Product overview
CHINT 252515 NU6-IIG/F is a Type 2 surge protective device for single-phase TT distribution circuits. This 1P+N version combines a 275 V AC phase cartridge with an N–PE cartridge and includes remote fault signalling. Its phase-module maximum discharge current is 40 kA, with a nominal discharge current of 20 kA, both at an 8/20 µs waveform.
Technical selection summary
| Ordering code | 252515 |
|---|---|
| Manufacturer model | NU6-IIG/F 40/275 1P+N |
| SPD test class | Type 2 / Class II |
| Poles | 1P+N |
| Maximum continuous operating voltage Uc | 275 V AC (phase module); 255 V AC (N–PE module) |
| Maximum discharge current Imax (8/20 µs) | 40 kA (L–N); 65 kA (N–PE) |
| Nominal discharge current In (8/20 µs) | 20 kA (L–N); 30 kA (N–PE) |
| Voltage protection level Up | 1.5 kV |
| Remote signalling | Yes; 1NO+1NC changeover contact |
| Auxiliary contact rating | 250 V AC, 0.5 A |
| Frequency | 50/60 Hz |
| Cartridge status indication | Green: OK; red: fault |
| Construction | Removable protective cartridges and base |
| Application | TT single-phase circuits; L–N and N–PE protection |
| Reference standard | IEC/EN 61643-11 |
| EAN | 6941498993402 |
| Package quantity | 6 pieces; 90 pieces per carton |
Product features
- Removable protective cartridges with a visual status window.
- Separate L–N and N–PE protection paths for the 1P+N arrangement.
- Remote changeover contact for external status monitoring.
- Modular construction for low-voltage distribution panels.
Typical applications
- Single-phase TT building distribution panels.
- Distribution sub-panels supplying sensitive electrical equipment.
- Protection against transient overvoltage from lightning and switching events.