CHINT · Motor Protection Circuit Breaker
Product overview
CHINT 495189 NS2-25X/2C is a three-pole motor protection circuit breaker with a 20–25 A adjustable thermal setting and rotary handle control. It provides motor switching with overload and short-circuit protection.
Technical selection summary
| Ordering code | 495189 |
|---|---|
| Manufacturer model | NS2-25X/2C |
| Reference standard | IEC/EN 60947-2 |
| Poles | 3P |
| Rated current (In) | 25 A |
| Rated voltage | 230/400/690 V AC |
| Frequency | 50/60 Hz |
| Insulation voltage (Ui) | 690 V AC |
| Impulse withstand voltage (Uimp) | 8 kV |
| Maximum operating voltage | 690 V AC |
| Ultimate breaking capacity (Icu) | 15 kA — verify at actual operating voltage |
| Service breaking capacity (Ics) | 7.5 kA — verify at actual operating voltage |
| DIN modules | 2.5 |
| Ingress protection | IP20 |
| Dimensions (H × W × D) | 91.3×44.5×94.9 mm |
| AC-3 motor power at 230V | 5.5 kW |
| AC-3 motor power at 400V | 11 kW |
| AC-3 motor power at 690V | 18.5 kW |
| Current adjustment (Ir) | 20–25 A |
| Control | Rotary handle |
| Compatible accessories | Undervoltage releases, series NS2-UV. Shunt releases, series NS2-SH. Front-mounted auxiliary contacts, series NS2-AE. Side-mounted auxiliary contacts, series NS2-AU. Side-mounted fault signalling contacts, series NS2-FA. |
| Units per pack | 1 |
| Units per carton | 60 |
| EAN | 6925808320232 |
| Ambient temperature | −5 to +40 °C |
| Maximum altitude | 2,000 m |
Confirm Icu and Ics for the actual system voltage against the supplied unit’s nameplate before selection.
Typical applications
- Machine motor feeders
- Pump and fan motor protection
- Manual motor control panels