CHINT · Molded Case Circuit Breaker
Product overview
CHINT 263112 is a 4-pole EN electronic molded case circuit breaker for industrial AC distribution. The 1600 A frame contains a 1250 A release for overload and short-circuit protection.
Model and trip unit
NM8N-1600S-EN-1250/4/25 identifies the 1600 A frame, S breaking-capacity class, 1250 A rated current and 4-pole Frame 25 configuration. The long-time pickup adjustment for this code is 0.4 – 1 x In.
Technical selection summary
| Ordering code | 263112 |
|---|---|
| Manufacturer model | NM8N-1600S-EN-1250/4/25 |
| Standard | EN 60947-2 |
| Poles | 4P |
| Rated current (In) | 1250 A |
| Rated voltage | 380/415 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Impulse withstand voltage (Uimp) | 8 kV |
| Maximum operating voltage | 690 V AC |
| Ultimate breaking capacity (Icu) | 50 kA (AC380/400/415V) |
| Service breaking capacity (Ics) | 50 kA (AC380/400/415V) |
| Power dissipation | 250 W |
| Degree of protection | IP00 / IP40 with terminal covers |
| Thermal adjustment (Ir) | 0.4 – 1 x In |
| Utilization category | B |
| Trip unit | EN basic electronic release |
| Frame designation | Frame 25 |
| Units per pack | 1 |
| Units per carton | 1 |
| EAN | 6932103891930 |
| ETIM | EC000228 |
| Dimensions (H × W × D) | 286 × 280 × 167 mm |
Short-circuit ratings by voltage
| Operating voltage | Icu | Ics |
|---|---|---|
| 380 / 400 / 415 V AC | 50 kA | 50 kA |
Typical applications
- Industrial power distribution panels and power centers
- Feeder protection in motor control centers