Photovoltaic DC switch-disconnector
Product overview
Four-pole rotary switch-disconnector for photovoltaic DC circuits, with non-polarized contacts and a lockable OFF position. Mount the MD switch body on DIN rail inside a suitable enclosure.
Technical selection summary
| Model | ISO-40 MD |
|---|---|
| Mounting | DIN rail, unenclosed switch body |
| Poles | 4 |
| Rated operational voltage | 1000 V DC for this listing |
| Rated operational current at 1000 V DC | 32 A with all four poles in series on one load |
| Insulation voltage (Ui) | 1500 V |
| Impulse withstand voltage (Uimp) | 8 kV |
| Utilization categories on the nameplate | DC-PV2 and DC-21B |
| Switch body protection | IP20 |
| Standard referenced on nameplate | IEC/EN 60947-3 |
| Contact gap per pole | 8 mm |
| Main terminal numbers | 1, 3, 5, 7 and 2, 4, 6, 8 |
| Rigid conductors (solid or stranded) | 4–16 mm² |
| Flexible conductors | 4–10 mm² |
| Conductors per terminal | 1, prepared before insertion |
| Stripping length | 8 mm |
| M4 terminal screw torque | 1.2–1.8 N·m per the M4 terminal drawing. Check the unit instructions before tightening. |
DC-PV2 operating current by voltage and wiring
| DC voltage | Two loads, two poles in series per load | One load, four poles in series |
|---|---|---|
| 300 V | 32 A | 32 A |
| 600 V | 32 A | 32 A |
| 800 V | 16 A | 32 A |
| 1000 V | 9 A | 32 A |
This listing covers the four-pole MD version at 1000 V DC and 32 A with all four poles in series on one load. The two-load column is a series catalogue reference. Use the wiring and temperature derating instructions for the supplied switch before installation.
Typical applications
- PV array disconnection on the DC side of a solar inverter.
- DIN-rail installation inside a PV distribution enclosure.
DIN-rail product and mounting dimensions
The product image shows the manufacturer catalogue DIN-rail housing and actuator.
Wiring and temperature references
The wiring sheet includes alternate factory arrangements. The temperature plot is a catalogue reference for the DC-21B and DC-PV1 curves shown in its legend.
Other mounting versions
Door-interlock and panel-mounted versions have different actuator assemblies and mounting dimensions. Their drawings are provided for comparison. The separate MD-B faceplate variant has a different actuator and should be specified separately.