DELIXI · Bar fuse-switch disconnector
Product overview
DELIXI CDHR16 is a three-pole bar fuse-switch disconnector. The manufacturer distinguishes linked three-phase operation from separate single-pole operation and separately codes fuse-link, direct-knife and empty-carrier arrangements.
Technical selection summary
| Brand and series | DELIXI CDHR16 |
|---|---|
| Current stages / poles | 160, 250, 400 or 630 A; 3P |
| Operating / insulation voltages | Ue 500/690 V AC; Ui 800 V |
| Utilization category | AC-22B |
| Conditional short-circuit rating | 100 kA at 500 V AC; 50 kA at 690 V AC, with the matching fuse arrangement |
| Operation suffix | L: linked three-phase operation; default: separate single-pole operation |
| Combination suffix | DT: supplied with fuse link; DZT: direct knife; default: without fuse link/knife |
| Fuse-link size by current stage | 160 A: RT16-00 / NT00; 250 A: RT16-1 / NT1; 400 A: RT16-2 / NT2; 630 A: RT16-3 / NT3 |
| Construction / installation | Base and fuse-carrier cover; match the exact linked/separate drawing and busbar installation |
| Reference standards | IEC 60947-3; GB/T 14048.3 |
Conditional short-circuit ratings depend on the correct fuse coordination and voltage. A direct-knife version does not provide the fuse-link protection of a DT assembly. Confirm operation and combination suffixes before specifying dimensions or protection.
Typical applications
- Fuse-protected distribution circuits with the correct coordinated assembly
- Bar-mounted distribution equipment using the specified operation arrangement