NewTrend · Motor protection circuit breakers
Product overview
NewTrend GV2ME, GV2P and GV3ME manual motor protection breakers. Match the exact breaker model and thermal-current setting before selecting the short-circuit rating.
Technical selection summary
| Supply identity | NewTrend/OEM. The specified technical reference parameters apply; original-brand approvals are not inherited. |
|---|---|
| Model families | GV2ME pushbutton, GV2P rotary handle and legacy GV3ME pushbutton. GV3P is not included. |
| Protection | Thermal-magnetic motor protection; adjustable thermal setting; 3 poles; 50/60Hz |
| Selection | Select Current Setting first, then the available Model. Values below are matched to that exact model. |
| Short-circuit conditions | The Icu and Ics values below apply only at AC400/415V. They are not universal ratings at every voltage. Rows marked above100kA in the GV2 source are conservatively shown as100kA minimum. |
| Control supply | Manual motor breaker; no contactor control-coil voltage is required. |
| Dimensions | GV3ME reference:61.2mm wide,120mm high and113mm deep. GV2 has a different outline; see the separate frame drawings. |
| Mounting / wiring | 35mm DIN rail or suitable panel mounting; 3 main poles. Optional releases and auxiliary contacts require separately matched references. |
OEM supply uses the specified reference parameters. Schneider/Telemecanique branding and approvals in the reference documents describe those original products, not NewTrend certification. Different families have different accessories and dimensions.
Model and rating matrix at AC400/415V
| Model | Current setting | Icu | Ics |
|---|---|---|---|
| GV2ME01 | 0.1-0.16A | 100kA | 100kA |
| GV2ME02 | 0.16-0.25A | 100kA | 100kA |
| GV2ME03 | 0.25-0.4A | 100kA | 100kA |
| GV2ME04 | 0.4-0.63A | 100kA | 100kA |
| GV2ME05 | 0.63-1A | 100kA | 100kA |
| GV2ME06 | 1-1.6A | 100kA | 100kA |
| GV2ME07 | 1.6-2.5A | 100kA | 100kA |
| GV2ME08 | 2.5-4A | 100kA | 100kA |
| GV2ME10 | 4-6.3A | 100kA | 100kA |
| GV2ME14 | 6-10A | 100kA | 100kA |
| GV2ME16 | 9-14A | 15kA | 7.5kA |
| GV2ME20 | 13-18A | 15kA | 7.5kA |
| GV2ME21 | 17-23A | 15kA | 6kA |
| GV2ME22 | 20-25A | 15kA | 6kA |
| GV2ME32 | 24-32A | 10kA | 5kA |
| GV2P01 | 0.1-0.16A | 100kA | 100kA |
| GV2P02 | 0.16-0.25A | 100kA | 100kA |
| GV2P03 | 0.25-0.4A | 100kA | 100kA |
| GV2P04 | 0.4-0.63A | 100kA | 100kA |
| GV2P05 | 0.63-1A | 100kA | 100kA |
| GV2P06 | 1-1.6A | 100kA | 100kA |
| GV2P07 | 1.6-2.5A | 100kA | 100kA |
| GV2P08 | 2.5-4A | 100kA | 100kA |
| GV2P10 | 4-6.3A | 100kA | 100kA |
| GV2P14 | 6-10A | 100kA | 100kA |
| GV2P16 | 9-14A | 100kA | 100kA |
| GV2P20 | 13-18A | 50kA | 50kA |
| GV2P21 | 17-23A | 50kA | 50kA |
| GV2P22 | 20-25A | 50kA | 50kA |
| GV3ME06 | 1-1.6A | 100kA | 100kA |
| GV3ME07 | 1.6-2.5A | 100kA | 100kA |
| GV3ME08 | 2.5-4A | 100kA | 100kA |
| GV3ME10 | 4-6A | 100kA | 100kA |
| GV3ME14 | 6-10A | 100kA | 100kA |
| GV3ME20 | 10-16A | 100kA | 50kA |
| GV3ME25 | 16-25A | 100kA | 50kA |
| GV3ME40 | 25-40A | 35kA | 17.5kA |
| GV3ME63 | 40-63A | 35kA | 17.5kA |
| GV3ME80 | 56-80A | 15kA | 7.5kA |
Complete GV2 reference catalogue
Typical applications
- Matched electrical protection and control installations
Open complete technical reference
Product reference images and drawings
Legacy GV3ME voltage-specific breaking-capacity table. Ics percentages apply to Icu.
Legacy GV3ME dimensions and mounting reference in mm.
Legacy GV3ME main and optional accessory circuit diagrams. Accessories are ordered separately.
GV2 family technical reference; these outlines are separate from GV3ME.